VRV IV VRT Advantages
The graphs below are intended only to depict how new Daikin VRV IV efficiency is increased by using VRT.
Up to 28%
Improved Seasonal
Cooling Efficiency
vs. VRV III
Specicaons are subect to change at any me. United Refrigeraon is not responsible for changes, errors & omissions.
52
Technical Data for VRV IV Heat Pump Outdoor Units
6 Ton 8 Ton 10 Ton 12 Ton 14 Ton
Model
208-230V/3Ph/60Hz RXYQ72TATJU RXYQ96TATJU RXYQ120TATJU RXYQ144TATJU RXYQ168TATJU
460V/3Ph/60Hz RXYQ72TAYDU RXYQ96TAYDU RXYQ120TAYDU RXYQ144TAYDU RXYQ168TAYDU
Performance
Rated Cooling Capacity Btu/h 69,000 92,000 114,000 138,000 160,000
Rated Heating Capacity Btu/h 73,000 103,000 129,000 154,000 176,000
Operation Range - Cooling °F DB 10*-122 10*-122 10*-122 10*-122 10*-122
Operation Range - Heating °F WB -4 - 60 -4 - 60 -4 - 60 -4 - 60 -4 - 60
Sound Pressure dB(A) 58 61 61 64 65
IEER (Ducted / Non-Ducted) 20.7 / 25.9 22.5 / 27.3 22 / 25.4 22.6 / 24.8 19.8 / 22.6
Airflow cfm 5,544 5,827 6,286 8,228 8,228
Refrigerant Piping
Vertical Pipe Length Above ft. 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting)
Vertical Pipe Length Below ft. 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting)
Vertical Pipe Length Between IDU ft. 100 100 100 100 100
Actual Pipe Length ft. 540 540 540 540 540
Equivalent Pipe Length ft. 620 620 620 620 620
Total Pipe Length ft. 3,280 3,280 3,280 3,280 3,280
Unit Weight (RXYQ_TAT / RXYQ_TAY) lbs. 435 / 451 525 / 553 528 / 556 695 / 709
Dimensions (H x W x D) in. 66-11/16 x 36-11/16 x 30-3/16 66-11/16 x 48-7/8 x 30-3/16
16 Ton 18 Ton 20 Ton 22 Ton 24 Ton
Model
208-230V/3Ph/60Hz RXYQ192TATJU RXYQ216TATJU RXYQ240TATJU RXYQ264TATJU RXYQ288TATJU
460V/3Ph/60Hz RXYQ192TAYDU RXYQ216TAYDU RXYQ240TAYDU RXYQ264TAYDU RXYQ288TAYDU
Combination
1 x RXYQ120T 1 x RXYQ120T 2 x RXYQ120T 1 x RXYQ144T 2 x RXYQ144T
1 x RXYQ72T 1 x RXYQ96T 1 x RXYQ120T
Performance
Rated Cooling Capacity Btu/h 184,000 206,000 228,000 250,000 274,000
Rated Heating Capacity Btu/h 206,000 230,000 256,000 282,000 308,000
Operation Range - Cooling °F DB 23-122 23-122 23-122 23-122 23-122
Operation Range - Heating °F WB -4 - 60 -4 - 60 -4 - 60 -4 - 60 -4 - 60
Sound Pressure dB(A) 63 64 64 66 67
IEER (Ducted/Non-Ducted) 21.2 / 22.2 21.1 / 20.5 20.9 / 20.8 19.6 / 20.3 19.6 / 20.1
Airflow cfm 5,544 + 6,286 5,827 + 6,286 6,286 + 6,286 6,286 + 8,228 8,228 + 8,228
Refrigerant Piping
Vertical Pipe Length Above ft. 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting)
Vertical Pipe Length Below ft. 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting)
Vertical Pipe Length Between IDU ft. 100 100 100 100 100
Actual Pipe Length ft. 540 540 540 540 540
Equivalent Pipe Length ft. 620 620 620 620 620
Total Pipe Length ft. 3,280 3,280 3,280 3,280 3,280
Unit
Weight (RXYQ_TAT / RXYQ_TAY) lbs. 435 + 528 / 451 + 556 525 + 528 / 553 + 556 528 + 528 / 556 + 556 528 + 695 / 556 + 709 695 + 695 / 709 + 709
Dimensions (H x W x D) in. (66-11/16 x 48-7/8 x 30-3/16) +
(66-11/16 x 36-11/16 x 30-3/16) (66-11/16 x 48-7/8 x 30-3/16) x 2
26 Ton 28 Ton 30 Ton 32 Ton 34 Ton
Model
208-230V/3Ph/60Hz RXYQ312TATJU RXYQ336TATJU RXYQ360TATJU RXYQ384TATJU RXYQ408TATJU
460V/3Ph/60Hz RXYQ312TAYDU RXYQ336TAYDU RXYQ360TAYDU RXYQ384TAYDU RXYQ408TAYDU
1 x RXYQ168T 2 x RXYQ168T 3 x RXYQ120T 1 x RXYQ168T 1 x RXYQ168T
Combination
1 x RXYQ144T 1 x RXYQ120T 1 x RXYQ144T
1 x RXYQ96T 1 x RXYQ96T
Performance
Rated Cooling Capacity Btu/h 296,000 312,000 334,000 352,000 372,000
Rated Heating Capacity Btu/h 334,000 344,000 372,000 400,000 435,000
Operation Range - Cooling °F DB 23-122 23-122 23-122 23-122 23-122
Operation Range - Heating °F WB -4 - 60 -4 - 60 -4 - 60 -4 - 60 -4 - 60
Sound Pressure dB(A) 68 68 66 68 68
IEER (Ducted/Non-Ducted) 18.8 / 19.9 18.5 / 20.6 18.5 / 19.4 18.5 / 21.1 19.0 / 21.1
Airflow cfm 8,228 + 8,228 8,228 + 8,228 6,286 + 6,286 + 6,286 5,827 + 6,286 + 8,228 6,286 + 6,286 + 8,228
Refrigerant Piping
Vertical Pipe Length Above ft. 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting) 164 (295 w/outdoor setting)
Vertical Pipe Length Below ft. 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295 w/outdoor setting) 130 (295/w/outdoor setting) 130 (295 w/outdoor setting)
Vertical Pipe Length Between IDU ft. 100 100 100 100 100
Actual Pipe Length ft. 540 540 540 540 540
Equivalent Pipe Length ft. 620 620 620 620 620
Total Pipe Length ft. 3,280 3,280 3,280 3,280 3,280
Unit
Weight (RXYQ_TAT / RXYQ_TAY) lbs. 695 + 695 / 709 +709 695 + 695 / 709 +709 528 + 528 + 528 / 525 +528 + 695 525 + 528 + 695 / 553 + 556 + 709 525 + 695 + 695 / 553 + 709 + 709
Dimensions (H x W x D) in. (66-11/16 x 48-7/8 x 30-3/16) x 2 (66-11/16 x 48-7/8 x 30-3/16) x 3
For all equipment installation and application limitations please refer to the specific Engineering Data Books. * Application rules apply.
PF-VRV4 ACHP 01-17
VRV IV Operations
2017
Ambient Temperature
100%
75%
50%
25%
0%
68oF 77oF 86oF 95oF
LOAD
Cooling
Requirement
Design Condition
50
Variable Rt*
45
40
35
30 Fixed Rt*
25
20
15
68oF 77oF 86oF 95oF
EFFICIENCY
Ambient Temperature
*Data based on RXYQ96 outdoor unit only with 100% connection ratio.
Lower capacity
is required to cool
and heat a building
during mid-season.
A VRV system adapts to
the required changes in
capacity by varying the
refrigerant volume. This results
in an increase in efficiency at
part load operation.
The efficiency of the
VRV IV system is further
increased by adjusting the
refrigerant temperature
depending on space load
and weather conditions.