FBQ Series Ducted Indoor Specicaons
Model FBQ18PVU FBQ24PVU FBQ30PVU FBQ36PVU FBQ42PVU
Max ESP Up to .80
Cooling Capacity 18,000 24,000 30,000 36,000 42,000
Heang Capacity 20,000 27,000 34,000 40,000 47,000
Air Flow 529/582/635 565/618/688 706/794/882 812/953/1130 988/1165/1377
Sound Pressure 37/39/41 38/40/42 39/41/43 39/41/43 40/42/44
Maximum Over Current Protecon 15 15 15 15 15
Dimensions 11 13/16 x 38 3/8 x 27 9/16 11 13/16 x 55 1/8 x 27 9/16
Weight 80 lb 102 lb
RZ Series Outdoor Specicaons
Model RZ18PVU RZ24PVU RZ30PVU RZ36PVU RZ42PVU
Sound Pressure 49/49 58/58
Operang Range Cooling Low Ambient 23 - 115
Operang Range Cooling Low
Ambient with Wind Bae 0 - 115
Operang Range Heang (RZQ only) 0 - 77
Maximum Over Current Protecon 20 20 20 30 30
Dimensions 30 5/16 x 35 7/16 x 12 5/8 52 15/16 x 35 7/16 x 12 5/8
Weight 150 lb 283 lb
Part # Descripon Compatable with
DZK030E4 4 Zones FBQ18, 24 & 30
DZK030E5 5 Zones FBQ18, 24 & 30
DZK048E4 4 Zones FBQ36 & 42
DZK048E6 6 Zones FBQ36 & 42
DZKMTS1W Main Thermostat (required)
DZK2TS1W Thermostat for addional zones (oponal)
Specicaons are subect to change at any me. United Refrigeraon is not responsible for changes, errors & omissions.
Accessories
UL16x36 Condenser Pad
DACAWB3 Wall Bracket
AGG30X50 Aux Drain Pan
AGG30X60 Aux Drain Pan
AG1201+ Aux Drain Pan Switch
Control Opons
(Control is not included with the system)
BRC1E73 Navigaon Remote Controller
BRC2A71 Simplied Control
BRC4C82 Wireless Remote Control (FBQ)
KRCSO11B Remote Sensor
KRCSPW40 RS Cable 40’
KRCSPW80 RS Cable 80’
AG3000 Intermac Surge Protector
Wind Baes
For Low Ambient Cooling Applicaons
KPW5E80 All RZR & RZQ
(36 & 42 models have 2 fans & require 2 wind baes)
FBQ INVERTER DUCTED
Specicaons
38
Components sold separately
A Zoning Box (mounted on the Indoor Unit discharge
side), a Main Zone Thermostat and wireless Zone
Thermostats.
• The Zoning Box is a plenum with motorized zone
dampers that constantly modulate the condioned
air ow into each zone through standard ductwork
in response to the demand from the individual Zone
Thermostat.
• The Main Zone Thermostat is a wired color touch
display master unit used to congure the DZK system. It
can also be used as a thermostat for one of the zones.
• The Zone Thermostat is a baery-powered touch
display unit that is used for one zone. Each Zone
Thermostat monitors and allows the user to select a
comfortable room temperature and program or adust
the control funcons (scheduling,venlaon, etc.) for the
room.
For FBQ ducted indoor units
See more installaon supplies & accessories starng on page 59.
WHOLE HOUSE DUCTED HORIZONTAL 1842